How UPS Backup Time Is Calculated

How long the battery keeps the fans on during load shedding depends on how much energy it can safely give, how much the inverter loses, and how much power your appliances draw. The calculator uses one formula:

Backup hours = battery voltage (V) × capacity (Ah) × usable depth of discharge × 0.85 inverter efficiency ÷ load (W)

Worked example: a tubular battery on a typical load

Take a 12 V 150 Ah tubular battery running two ceiling fans, a few lights and a Wi-Fi router, about 350 W in total:

12 × 150 × 0.5 × 0.85 ÷ 350 ≈ 2.2 hours, or a little over two hours.

For comparison, a 12 V 100 Ah lithium battery on the same load gives 12 × 100 × 0.8 × 0.85 ÷ 350 ≈ 2.3 hours. A smaller lithium battery can match a larger lead-acid one because more of its capacity is usable.

Real backup is usually somewhat lower

Treat the result as a best case. Real backup is usually somewhat shorter: batteries lose capacity with age, hot or cold rooms reduce what they deliver, the inverter draws some power for itself even when idle, and a battery not fully recharged after the last outage starts with less. Lead-acid and tubular batteries lose capacity noticeably over a few years.

Choosing the Right UPS or Inverter Size

The battery decides how long you get power; the inverter decides how much you can run at once. The calculator recommends an inverter rated for your total running watts × 1.25, so it is not working at its limit all the time. It also shows the approximate VA rating, using VA ≈ W ÷ 0.8, because many UPS units are sold by VA rather than watts.

For the 350 W example: 350 × 1.25 ≈ 440 W, and 440 ÷ 0.8 ≈ 550 VA. You would look for the next standard size above that. Manufacturers state ratings differently, so always check the spec sheet for the continuous watt rating, not just the VA figure on the box.

Starting surge from motors and compressors

Appliances with a motor or compressor, such as refrigerators, air conditioners, washing machines and water pumps, can briefly draw 2–3× their running watts when they start. That is a typical rule of thumb rather than an exact figure. If the inverter cannot handle the surge it may trip on overload, so check its surge rating before connecting these appliances.

Getting More Backup During Load Shedding

Series wiring: 12 V, 24 V and beyond

Larger inverters often need 24 V or more. Two 12 V batteries wired in series give 24 V at the same Ah: two 12 V 150 Ah batteries in series make a 24 V 150 Ah bank, holding twice the energy of one battery. Enter the bank's total voltage and Ah in the calculator, use matching batteries, and have an electrician do the wiring.

Want to know what your UPS load costs to recharge from the grid? Add your appliances to the electricity bill calculator. If you are thinking about panels and batteries to ride out load shedding, try the Solar ROI calculator and read our guide to solar in Pakistan.


Frequently Asked Questions

How long will a 150 Ah battery last on a UPS?

It depends on the load. A 12 V 150 Ah tubular battery running about 350 W (two fans, lights and a router) gives roughly 2.2 hours using this calculator's assumptions of 50% usable depth of discharge and 85% inverter efficiency. Real backup is usually somewhat lower.

Why is my actual backup shorter than the calculator says?

The calculator gives a best-case estimate. Batteries lose capacity with age, heat and cold reduce what they can deliver, the inverter uses some power just to stay on, and a battery that was not fully recharged after the last outage starts with less energy.

Is a lithium battery better than a tubular battery for load shedding?

A lithium (LiFePO4) battery lets you use more of its capacity: the calculator assumes 80% usable depth of discharge for lithium and 50% for lead-acid or tubular. So a smaller lithium battery can give similar backup to a larger tubular one. Compare prices and warranties before you buy.

What size UPS or inverter do I need?

Add up the running watts of everything you want on at the same time and multiply by 1.25 for headroom. To convert to VA, divide the watts by 0.8. For a 350 W load that is about 440 W, or roughly 550 VA. Check the inverter's spec sheet for its continuous and surge ratings.

Can I run a fridge, AC or water pump on my UPS?

Only if the inverter can handle their starting surge. Motors and compressors can briefly draw 2 to 3 times their running watts when they start, as a typical rule of thumb. A small home UPS may trip on that surge, and ACs and pumps drain the battery quickly.

What happens if I connect two 12 V batteries in series?

Wiring two 12 V batteries in series gives 24 V with the same Ah rating, so two 12 V 150 Ah batteries become a 24 V 150 Ah bank with twice the stored energy. Your inverter must be designed for 24 V.